PLC Oxygen Flow Controls

 

ECO2 SuperOxygenation Operation

The ECO2 PLC monitors the force main water flow. Based upon this flow, the PLC calculates an instantaneous Hydraulic Retention Time (HRT) of the waste water inside the force main. This HRT equates to an oxygen uptake rate of the force main. The PLC then adjusts the oxygen feed rate into the ECO2 system by means of the Oxygen Mass Flow Meter to match the oxygen uptake rate.

The PLC also monitors sidestream pump operation, side stream water flow, oxygen flow, ECO2 system water pressure, and water temperature and % oxygen in building. These parameters are checked against design inputs to ensure optimal system performance, system shutdown and alarm notification if operation is out of tolerance.

ECO2 PLC Control Components

PLC, Panel View Screen, Oxygen Mass Flow Meter, Visual Rotometer, two Solenoid Valves, two Check Valves, two Isolation Valves, % Oxygen Gas Sensor Side Stream Flow Meter, Alarm Capability, Data Logging / Trending, Pressure Sensor Temperature Sensor.

 

 
 